Chapter 20
Troubleshooting Your System

20–2

When an Error Exists

If an error exists within the controller, the controller LEDs operate as
described in the following tables.

The

Following

Error Exists

Probable Cause

Recommended Action

No input

er r

No Line Power

Verify proper line voltage and connections to the
controller.

power or
power supply
error

Power Supply Overloaded

This problem can occur intermittently if power
supply is overloaded when output loading and
temperature varies.

The

Following

Error Exists

Probable Cause

Recommended Action

Hardware
fa

Controller Memory Error

Cycle power. Contact your local Allen-Bradley
representative if the error persists.

fault

Loose Wiring

Verify connections to the controller.

The

Following

Error Exists

Probable Cause

Recommended Action

Application
fault

Hardware/Software Major
Fault Detected

1. Monitor Status File Word S6 for major error

code.

2. Remove hardware/software condition causing

fault.

3. Use the hot key sequence

FAULT

-

DEL

to

clear the fault.

4. Attempt to enter RRUN, RCSN, or RSSN

mode. If unsuccessful, repeat recommended
action steps above or contact your local
Allen-Bradley distributor.

If the LEDs indicate:

FAULT

FORCE

POWER

RUN

If the LEDs indicate:

FAULT

FORCE

Й

ЙЙ

Й Й

ЙЙ

POWER

RUN

Й Й

ЙЙ

ЙЙ

Refer to the following key to determine
the status of the LED indicators:

Indicates the LED is OFF.
Indicates the LED is ON.

Indicates the LED is FLASHING.

Status of LED does not matter.

If the LEDs indicate:

FAULT

FORCE

ЙЙ

Й

Й

ЙЙ

ЙЙ

Й

Й

Й

Й

ЙЙ

ЙЙ

POWER

RUN

Й

Й

Й

Й