Identifying controller faults – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 379

Advertising
background image

Label

Fault Code (Hex)

Advisory Message

Chapter 20
Troubleshooting Your System

20–11

While a program is executing, a fault may occur within the operating system
or your program. When a fault occurs, you have various options to
determine what the fault is and how to correct it. This section describes how
to clear faults and provides a list of possible advisory messages with
recommended corrective actions.

Clearing Controller Faults

There are three ways you can clear a fault:

manually, by viewing the fault display

automatically, using the Fault Override bit (S1/8) or the Run Always bit
(S1/12) and cycling power

implementing the user-fault routine and clearing bit S1/13 within it

Manually Clearing Faults

You can manually view and clear a fault by accessing the fault display.

F L T :

x x x x H

<

m e s s a g e

>

Follow these steps to manually clear a fault:

1. From any of the functional areas, access the fault display.

FAULT

PRE/LEN

F L T :

0 0 2 0 H

M I N O R

E R R

A T

E N D

If you press this key and a fault does not exist, the message

NO MAJOR

FAULT

is displayed. Press any key to return to the previous screen.

Identifying Controller Faults