Label
Fault Code (Hex)
Advisory Message
Chapter 20
Troubleshooting Your System
20–11
While a program is executing, a fault may occur within the operating system
or your program. When a fault occurs, you have various options to
determine what the fault is and how to correct it. This section describes how
to clear faults and provides a list of possible advisory messages with
recommended corrective actions.
Clearing Controller Faults
There are three ways you can clear a fault:
•
manually, by viewing the fault display
•
automatically, using the Fault Override bit (S1/8) or the Run Always bit
(S1/12) and cycling power
•
implementing the user-fault routine and clearing bit S1/13 within it
Manually Clearing Faults
You can manually view and clear a fault by accessing the fault display.
F L T :
x x x x H
<
m e s s a g e
>
Follow these steps to manually clear a fault:
1. From any of the functional areas, access the fault display.
FAULT
PRE/LEN
F L T :
0 0 2 0 H
M I N O R
E R R
A T
E N D
If you press this key and a fault does not exist, the message
NO MAJOR
FAULT
is displayed. Press any key to return to the previous screen.