Chapter 11
Using Data Handling Instructions

11–12

Using FLL

The following figure shows how file instruction data is manipulated. The
instruction fills the words of a file with a source value. It uses no status bits.
If you need an enable bit, program a parallel output that uses a storage
address.

Source

Destination

Word to File

Entering Parameters

Enter the following parameters when programming this instruction:

Source is a constant or element address. The file indicator (#) is not
required for an element address.

Destination is the starting address of the file you want to fill. You must
use the file indicator (#) in the address.

Length is the number of words or elements in the file to be filled.

If th d tination fil t p i a:

then you can specify a maximum length of:

If the destination file type is a:

Discrete

Analog

Output

1

5

Input

2

8

Status

33

Bit

32

Timer

40

Counter

32

Control

16

Integer

105

All elements are filled from the source value (typically a constant) into the
specified destination file each scan the rung is true. Elements are filled in
ascending order.

Entering the Instruction

You enter the instruction from within the program monitor functional area.
The following items apply when entering the instruction:

Whenever you see asterisks on the display, the HHP is waiting for data
entry (i.e., a number).

You can return to previously entered operands by pressing this key:

Then if you want to edit that operand, press

DEL

or

FUN-DEL

and enter

new parameters. Press

ENT

to accept the operand and move on to the next

one. Once the entire instruction is entered, if you want to edit the