Chapter 8
Using Basic Instructions

8–13

The example below illustrates when you would enter the ANB instruction.

a

e

b

c

d

NEW RUNG
LD a
OR b
LD c
OR d

 ANB

OUT e

Instruction List



Using ORB

The ORB instruction is used to make a parallel connection of circuit blocks
with two or more contacts. (A parallel connection of circuit blocks with one
contact requires only an OR or ORI instruction. See page 16–2.)

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 0

O R B

The example below illustrates when you would enter the ORB instruction.

a

b

e

c

d

NEW RUNG
LD a
AND b
LD c
AND d

 ORB

OUT e

Instruction List





ORB

+ -

/

To access the ORB instruction, press: