Chapter 14
Using High-Speed Counter Instructions

14–14

When a low preset is reached, the:

LP bit is set.

High-speed counter interrupt file (file 4) is executed if the interrupt is
enabled. The IL bit is set and the IH, IN, and IV bits are reset.

An overflow occurs when the hardware accumulator transitions from

+

32,767 to –32,768. When an overflow occurs, the:

OV bit is set.

High-speed counter interrupt file (file 4) is executed if the interrupt is
enabled. The IV bit is set and the IH, IL, and IN bits are reset.

An underflow occurs when the hardware accumulator transitions from
–32,768 to

+

32,767. When an underflow occurs, the:

UN bit is set.

High-speed counter interrupt file (file 4) is executed if the interrupt is
enabled. The IN bit is set and the IH, IL, and IV bits are reset.

The following tables summarize what the input state must be for the
corresponding high-speed counter action to occur:

Bidirectional Counter (Encoder)

Input State

High-Speed

Count r ction

Input A (I/0)

Input B (I/1)

HSC Rung

High-Speed

Counter Action

Turning On

Off

True

Count Up

Turning Off

Off

True

Count Down

NA

On

NA

Hold Count

NA

NA

False

Hold Count

NA (Not Applicable)

Bidirectional Counter with Reset and Hold (Encoder)

Input State

High-Speed

Count r

Input A (I/0)

Input B (I/1)

Input Z (I/2)

Input Hold

(I/3)

HSC Rung

High-Speed

Counter

Action

Turning On

Off

Off

Off

True

Count Up

Turning Off

Off

Off

Off

True

Count Down

Off or On

NA

Off

NA

NA

Hold Count

NA

On

Off

NA

NA

Hold Count

NA

NA

Off

NA

False

Hold Count

NA

NA

Off

On

NA

Hold Count

Off

Off

On

NA

NA

Reset to 0

NA (Not Applicable)

➀ The optional hardware high-speed counter reset is the logical coincidence of A x B x Z.