Control block layout – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 287

Advertising
background image

Chapter 15
Using Communication Protocols

15–3

The following table illustrates combinations of message types and target
devices and their valid file types.

Command Type

Message

Type

Initiating Device

Valid File

Types

Target Device

➀➁➂

Valid File Types

SLC500/ML1000

Write

MicroLogix 1000

O,I,S,B,T,C,R,N

MicroLogix 1000

O,I,S,B,T,C,R,N

SLC500/ML1000

Read

MicroLogix 1000

O,I,S,B,T,C,R,N

MicroLogix 1000

O,I,S,B,T,C,R,N

CIF

Write

MicroLogix 1000

O,I,S,B,T,C,R,N

MicroLogix 1000

N7

CIF

Read

MicroLogix 1000

O,I,S,B,T,C,R,N

MicroLogix 1000

N7

SLC500/ML1000

Write

MicroLogix 1000

O,I,S,B,T,C,R,N

SLC 500

O

,I

,S,B,T,C,R,N

SLC500/ML1000

Read

MicroLogix 1000

O,I,S,B,T,C,R,N

SLC 500

O

,I

,S,B,T,C,R,N

CIF

Write

MicroLogix 1000

O,I,S,B,T,C,R,N

SLC 500

N9

CIF

Read

MicroLogix 1000

O,I,S,B,T,C,R,N

SLC 500

N9

The DF1 Full-Duplex protocol can be used if the target device supports it. Such devices include MicroLogix
1000 controllers (any series), SLC 5/03, SLC 5/04 and SLC 5/05 processors, and PLC-5 processors (CIF
command type only).

The DH-485 protocol can be used if the target device supports it. Such devices include MicroLogix 1000
controllers (except for Series A and B discrete controllers) and SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, SLC
5/04 or SLC 5/05 processors.

The DF1 Half-Duplex protocol can also be used with Series D or later discrete and all analog MicroLogix 1000
controllers, but a master is required, such as an SLC 5/03, SLC 5/04 or SLC 5/05 processor.

SLC 500, SLC 5/01, and SLC 5/02 processors do not support O or I file access from a MSG instruction.
SLC 5/03, SLC 5/04 and SLC 5/05 processors do support O and I file access, but only when unprotected.

Control Block Layout

The control block layouts shown below illustrate SLC500/ML1000 type messages.

EN ST DN ER EW NR TO Error Code

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Reserved for length (in elements)

Control Block Layout – SLC500/ML1000

Word

0

1

2

File Number

File Type (O, I, S, B, T, C, R, N)

Element Number

Subelement Number

3

4

5

6

Node Number

Advertising