Identifying hhp errors, Hardware error messages – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 371

Advertising
background image

Label

Error Code (Hex)

Advisory Message

Program Verification Error Location
(file and rung numbers)

Chapter 20
Troubleshooting Your System

20–3

When an error occurs while accepting edits, the MicroLogix 1000 HHP
displays an error message screen as shown here:

E R R : x x x x H

f f / r r r

<

m e s s a g e

>

Use the tables in this section to find the error code and the associated
recommended action(s) you should take to clear the error. The tables are
grouped by error type as described in the table below.

If the error code begins with a

then the error type is

0

Hardware

1, 5, 6, or F

Communication

2

Miscellaneous

3

Program Verification

Hardware Error Messages

Error Code

(Hex)

Advisory Message

Description

Recommended Action

0001

HARDWARE
FAILURE

The HHP encountered a
ROM, RAM, or keypad

Disconnect the HHP from the
micro controller, then reconnect

0002

FAILURE

ROM, RAM, or keypad
failure.

micro controller, then reconnect
it. If the error persists, record
the error code and contact your

ca

e

ra e

0003

the error code and contact your
local Allen-Bradley
representative.

0004

NO CONTROLLER

The HHP cannot
establish a
communication link to
the micro controller.

Disconnect the HHP from the
micro controller, then reconnect
it. If the error persists, record
the error code and contact your
local Allen-Bradley
representative.

0006

MEM MOD MISSING

The HHP cannot
establish a connection to
the memory module.

Disconnect the HHP from the
micro controller. Then either
reconnect it, or replace the
memory module in the HHP
with a new one.

Identifying HHP Errors