After You’ve Entered Your Program

Chapter 18

18–10

Setting the STI Enabled Bit

This selection determines if execution of the STI is allowed.

When this bit is set to

NO

, execution of the STI is not allowed.

When this bit is set to

YES

, execution of the STI is allowed (provided the STI

setpoint is non-zero). If reset when an interrupt occurs, the STI subroutine
does not execute and the STI Pending bit is set. The STI Timer continues to
run when this bit is disabled. The STE instruction sets this bit. The STD
instruction clears this bit.

To change the bit setting:

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Access the program configuration menu.

3. Arrow up to the option

STI ENABLED

and select it.

5 times

ENT

S T I

E N A B L E D

Y E S

N O

4. Select the option

YES

and return to the home screen.

ENT

ESC

ESC

5. You must accept your program edits for this change to take affect. For

information on accepting edits, see page 18–21.