Appendix C
Valid Addresssing Modes and File Types
for Instruction Parameters

C–8

Instruction

Valid Value

Ranges

Valid File Types

Valid Addressing

Mode(s)

Instruction

Parameter

Description

NEQ

Not Equal

source A

direct, indexed direct

O, I, S, B, T, C, R, N

Not Applicable

source B

immediate, direct,
indexed direct

O, I, S, B, T, C, R, N

–32,768–32,767
f-min–f-max

NOT

Logical NOT

source

direct, indexed direct

O, I, S, B, T, C, R, N

Not Applicable

destination

direct, indexed direct

O, I, S, B, T, C, R, N

Not Applicable

OR

Or (bit input)

source bit

direct

O, I, S, B, T, C, R, N
(bit level)

Not Applicable

OR

Or (word output)

source A

direct, indexed direct

O, I, S, B, T, C, R, N

–32,768–32,767

source B

direct, indexed direct

O, I, S, B, T, C, R, N

–32,768–32,767

destination

direct, indexed direct

O, I, S, B, T, C, R, N

Not Applicable

ORI

Or Inverted

source bit

direct

O, I, S, B, T, C, R, N
(bit level)

Not Applicable

OSR

One-Shot Rising

bit address

direct

O, I, S, B, T, C, R, N

Not Applicable

OUT

Output (or Output
Energize)

bit address

direct

O, I, S, B, T, C, R, N

Not Applicable

RAC

HSC Reset
Accumulator

counter

direct

C

Not Applicable

source

immediate, direct

O, I, S, B, T, C, R, N

–32,768–32,767
f-min–f-max

RES

Reset (timer/counter)

structure

direct

T, C, R
(element level)

Not Applicable

RES

Reset (high-speed
counter)

structure

direct

T, C, R
(element level)

Not Applicable

RET

Return

Not Applicable

RST

Reset (or Output
Unlatch)

bit address

direct

O, I, S, B, T, C, R, N

Not Applicable

RTO

Retentive Timer

timer

direct

T (element level)

Not Applicable

time base

immediate

0.01 or 1.00

preset

(contained in the
timer register)

0–32,767

accum

(contained in the
timer register)

0–32,767

SBR

Subroutine

Not Applicable

Advertising