Chapter 13
Using Application Specific Instructions

13–24

File 4, Rung 2

Is identical to the previous rung except that it is only active when the
”hole selector switch” is in the ”5–hole” position.

FUN GRAPHIC PARAMETER
CODE SYMBOL MNEMONIC NAME ADDRESS VALUE FORCES
–––– ––––––– –––––––– –––– ––––––– ––––– ––––––
20 |–] [– LD
hole selector switch bit 0
I/9 0

23 –]/[– ANI

hole selector switch bit 1
I/10 0

152 SQO FILE #N55
MASK FFFFH

High Preset Value (counts to next hole)
DEST N7
5 hole preset sequencer
CTRL R5
LEN 7
POS 0000H

42 –(U)– RST
force the sequencer to increment on the next scan
R5/EN 1

File 4, Rung 3

➀➂

Is identical to the two previous rungs except that it is only active when
the ”hole selector switch” is in the ”7–hole” position.

FUN GRAPHIC PARAMETER
CODE SYMBOL MNEMONIC NAME ADDRESS VALUE FORCES
–––– ––––––– –––––––– –––– ––––––– ––––– ––––––
20 |–] [– LD
hole selector switch bit 0
I/9 0

22 –] [– AND
hole selector switch bit 1
I/10 0

152 SQO FILE #N62
MASK FFFFH

High Preset Value (counts to next hole)
DEST N7
7 hole preset sequencer
CTRL R6
LEN 9
POS 0000H

42 –(U)– RST
force the sequencer to increment on the next scan
R6/EN 1

This rung accesses I/O only available with 32 I/O controllers. Therefore, do not include this rung if you are using a 16
I/O controller.

This instruction accesses I/O only available with 32 I/O controllers. Therefore, do not include this instruction if you are
using a 16 I/O controller.

More rungs will be added to this subroutine at the end of chapter 14.