3–2
The 1761-CBL-HM02 Series B or higher cable with pinouts is shown below.
Use this cable to connect the MicroLogix 1000 HHP to the MicroLogix 1000
Programmable Controller.
3 6
8–pin Mini DIN
1 2
3
4
5
6 7 8
20188
4
2
1
5 8
8–pin Locking Mini DIN
7
Connects to the Controller
Connects to the HHP
8–Pin
8–Pin
1
3
4
5
6
7
8
2
+24V
–24V
RXD
TXD
GND
–24V
2
3
7
5
6
4
8
TXD
RXD
GND
+24V
1