Chapter 20
Troubleshooting Your System

20–5

Miscellaneous Error Messages

Error Code

(Hex)

Advisory Message

Description

Recommended Action

2000

NO RESPONSE

A communication error
occurred between the
HHP and the micro
controller.

Disconnect the HHP from the
micro controller, then reconnect
it. If the error persists, record
the error code and contact your
local Allen-Bradley
representative.

2001

INVALID DEVICE

The device that the HHP
is attached to is telling
the HHP that it is not a
micro controller.

Make sure your HHP is
connected to a micro controller.
If the error persists, record the
error code and contact your
local Allen-Bradley
representative.

Program Verification Error Messages

Error Code

(Hex)

Advisory Message

Description

Recommended Action

3000

MISSING SOR

The rung does not begin
with a start of rung
instruction.

Add a start of rung instruction to
the beginning of the rung using
the

NEW RUNG

key.

3001

INVALID INPUT

The first input instruction
on the rung is not a load
instruction (e.g., LD, LDI,
LD EQU).

Change the input instruction
immediately after the Start of
Rung instruction to a load
instruction.

3002

MISSING OUTPUT

The rung does not end
with an output
instruction.

Add the appropriate output
instruction to the end of the
rung.

3003

INVALID RUNG

An instruction or
instruction block needs
an ANB or ORB to
properly join it with the
previous input logic on
the rung.

Check that all instructions or
instruction blocks have been
properly joined to the previous
input logic on the rung with an
ANB or ORB.

3004

INVALID RUNG

An MPP is missing from
the rung.

Add an MPP at the proper
location.

3005

INVALID ORB

An ORB instruction is
illegally positioned on the
rung.

Move the ORB to the correct
location on the rung or remove
it if the application does not
require it.

3006

INVALID ANB

An ANB instruction is
illegally positioned on the
rung.

Move the ANB to the correct
location on the rung or remove
it if the application does not
require it.

3007

INVALID ORB, OR

The position of an OR or
ORB instruction after an
MPS, MRD, or MPP
instruction has created
an illegal rung.

Review and rewrite the
instruction list logic. Two rungs
may be required to implement
the desired functionality.