Chapter 1
Installing Your Controller

1–14

To remove your controller from the DIN rail:

2. Holding the controller, pry downward on

the latch until the controller is released
from the DIN rail.

1. Place a screwdriver in the DIN rail latch at

the bottom of the controller.

Side View

DIN
Rail

20147

Using Mounting Screws

To install your controller using mounting screws:

2. Secure the template to the mounting

surface. (Make sure your controller
is spaced properly.)

1. Use the mounting template from

page A–8.

5. Mount the controller.

4. Remove the mounting template.

3. Drill holes through the template.

Important: Leave the protective wrap

attached until you are
finished wiring the controller.

Mounting
Template

Protective Wrap
(remove after wiring)

Mounting Your Controller Vertically

Your controller can also be mounted vertically within an enclosure using
mounting screws or a DIN rail. To insure the stability of your controller, we
recommend using mounting screws.

To insure the controller’s reliability, the following environmental
specifications must not be exceeded.

Description:

Specification:

Operating
Temperature

0

°

C to +40

°

C (+32

°

F to +113

°

F)

Operating Shock
(Panel mounted)

9.0g peak acceleration (11

±

1 ms duration)

3 times each direction, each axis

Operating Shock
(DIN rail mounted)

7.0g peak acceleration (11

±

1 ms duration)

3 times each direction, each axis

DC input voltage derated linearly from +30

°

C (30V to 26.4V).

Note: When mounting your controller vertically, the nameplate should be
facing downward.

A

A

A

A

Top

Bottom

Side

Side

A. Greater than or equal
to 50.8 mm (2 in.).