Chapter 9
Using Comparison Instructions
9–11
True/False Status of the Instruction
If the Low Limit has a value equal to or less than the High Limit, the
instruction is true when the Test value is between the limits or is equal to
either limit. If the Test value is outside the limits, the instruction is false, as
shown below.
Example, low limit less than high limit:
Low
Limit
High
Limit
Instruction is True
when Test value is
Instruction is False
when Test value is
5
8
5 through 8
–32,768 through 4 and 9 through 32,767
False
True
False
–32,768
Low Limit
High Limit
+ 32,767
If the Low Limit has a value greater than the High Limit, the instruction is
false when the Test value is between the limits. If the Test value is equal to
either limit or outside the limits, the instruction is true, as shown below.
8
5
–32,768 through 5 and 8 through 32,767
6 and 7
Example, low limit greater than high limit:
Low
Limit
High
Limit
Instruction is True
when Test value is
Instruction is False
when Test value is
True
False
True
–32,768
High Limit
Low Limit
+ 32,767