After You’ve Entered Your Program

Chapter 18

18–9

Setting the STI Setpoint

The STI setpoint is the time between successive executions of the STI
subroutine. The allowable range is from 10 ms to 2550 ms (entered in 10 ms
increments). A setpoint of zero disables the setpoint function.

Important: The setpoint value must be a longer time than the execution

time of the STI subroutine file, or a minor error bit is set.

To change the setting:

1. Access the program configuration menu.

2. Arrow up to the option

STI SETPOINT

and select it.

ENT

6 times

S T I

S E T P O I N T

( x 1 0

m s )

0

3. Type in a new setpoint.

4. Enter the setpoint and return to the home screen.

ENT

ESC

ESC