Appendix F
Optional Analog Input Software Calibration

F–5

| | +MUL––––––––––––––––––––+ | |

| +–+MULTIPLY +–+ |

| | |Source A LO_CAL_VALUE| | |

| | | 0| | |

| | |Source B SLOPE_X10K| | |

| | | 0| | |

| | |Dest N7:98| | |

| | | 0| | |

| | +–––––––––––––––––––––––+ | |

| | +DDV–––––––––––––––+ | |

| +–+DOUBLE DIVIDE +––––––+ |

| | |Source 10000| | |

| | | 10000| | |

| | |Dest N7:99| | |

| | | 0| | |

| | +––––––––––––––––––+ | |

| | +SUB–––––––––––––––+ | |

| +–+SUBTRACT +––––––+ |

| | |Source A SCALE_LOW| | |

| | | 0| | |

| | |Source B N7:99| | |

| | | 0| | |

| | |Dest OFFSET| | |

| | | 0| | |

| | +––––––––––––––––––+ | |

| | Overflow| |

| | Trap | |

| | S2:5/0 | |

| +–––––––––––––––––––(U)–––––+ |

| |

Rung 2:3

| |

| |

| CONVERSION_ENABLE +SCL––––––––––––––––––––+ |

|––––] [–––––––––––––––––––––––––––––––––––––––––+–+SCALE +–+–|

| | |Source A ANALOG_IN| | |

| | | ?| | |

| | |Rate[/10000] SLOPE_X10K| | |

| | | ?| | |

| | |Offset OFFSET| | |

| | | ?| | |

| | |Dest ANALOG_SCALED| | |

| | +–––––––––––––––––––––––+ | |

| |

|–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|