Chapter 20
Troubleshooting Your System
20–9
Tracing an Address You Enter
To enter an address and trace it, press the key sequence shown here:
TRACE
S
address
MON
This type of tracing method can be invoked from any of the four functional
areas:
•
home screen
•
program monitor
•
data monitor
•
multi-point
Tracing an Address That is Displayed
You can trace the address that is currently displayed on the MicroLogix 1000
HHP by pressing the key shown here:
TRACE
S
You can invoke trace using this method from the following functional areas:
•
program monitor
•
data monitor
•
multi-point
Tracing Bit Addresses Versus Word Addresses
The following table outlines whether the trace feature finds a bit address or a
word address when invoked from any of the functional areas.
If the address entered or displayed is a(n):
Then the trace finds:
output, bit, integer, or status file address
only bit instructions referencing
that bit. To invoke the trace
feature, the current radix must be
binary.
timer, counter, or control address
any bit instructions or parameters
of word instructions referencing
that Timer, Counter or Control
element