Chapter 14
Using High-Speed Counter Instructions

14–11

Bidirectional Counter with Reset and Hold (Pulse/direction)

Input State

High-Speed

Count r

Input Count

(I/0)

Input

Direction (I/1)

Input Reset

(I/2)

Input Hold

(I/3)

HSC Rung

High-Speed

Counter

Action

Turning
Off-to-On

Off

Off, On, or
Turning Off

Off

True

Count Up

Turning
Off-to-On

On

Off, On, or
Turning Off

Off

True

Count Down

NA

NA

Off, On, or
Turning Off

NA

False

Hold Count

NA

NA

Off, On, or
Turning Off

On

NA

Hold Count

Off, On, or
Turning Off

NA

Off, On, or
Turning Off

NA

NA

Hold Count

NA

NA

Turning On

NA

NA

Reset to 0

NA (Not Applicable)

Bidirectional Counter (Up/down count)

Input State

High-Sp d

Input Up

Count (I/0)

Input Down

Count (I/1)

HSC Rung

High-Speed

Counter Action

Turning
Off-to-On

Off, On, or
Turning Off

True

Count Up

Off, On, or
Turning Off

Turning
Off-to-On

True

Count Down

NA

NA

False

Hold Count

NA (Not Applicable)

Bidirectional Counter with Reset and Hold (Up/down count)

Input State

High-Speed

Count r

Input Up

Count (I/0)

Input Down

Count (I/1)

Input Reset

(I/2)

Input Hold

(I/3)

HSC Rung

High-Speed

Counter

Action

Turning
Off-to-On

Off, On, or
Turning Off

Off, On, or
Turning Off

Off

True

Count Up

Off, On, or
Turning Off

Turning
Off-to-On

Off, On, or
Turning Off

Off

True

Count Down

NA

NA

Off, On, or
Turning Off

NA

False

Hold Count

NA

NA

Off, On, or
Turning Off

On

NA

Hold Count

Off, On, or
Turning Off

Off, On, or
Turning Off

Off, On, or
Turning Off

NA

NA

Hold Count

NA

NA

Turning On

NA

NA

Reset to 0

NA (Not Applicable)