Estimating Memory Usage for Your Control System

Use the following to calculate memory usage for your control system.

1. Determine the total instruction words used by the instructions in

your program and enter the result. Refer to the table on page B–16.

2. Multiply the total number of rungs by 0.75 and enter the result.

Do not count the Start of File or End of File screens in each file.

3. To account for controller overhead, use 177.

4. To account for application data, use 110.

5. Total steps 1 through 4. This is the estimated total memory usage of

your application system. Remember, this is an estimate, actual
compiled programs may differ by

±

12%.

Subtract the total memory usage from 1024.

The result of this calculation is the estimated total memory
remaining in your selected controller.

Important: The calculated memory usage may vary from the actual

compiled program by

±

12%.

Total Memory Usage:

6. To determine the estimated amount of memory remaining in the

controller you have selected, do the following:

177

110

1024

-

Total Memory
Remaining:

Total Memory Usage
(from above):

Execution Time Worksheet

Use this worksheet to calculate your execution time for logic program.

Procedure

Maximum Scan Time

1.

Input scan time, output scan time, housekeeping time, and forcing.

2.

Estimate your program scan time:

A.

Count the number of program rungs in your logic program and multiply by 6.

B.

Add up your program execution times when all instructions are true. Include interrupt routines in

this calculation.

3.

Estimate your controller scan time:

A.

Without communications, add sections 1 and 2

B.

With communications, add sections 1 and 2 and multiply by 1.05

4.

To determine your maximum scan time in ms, divide your controller scan time by 1000.

210

µ

s (discrete)

330

µ

s with forcing (analog)

250

µ

s without forcing (analog)

________

_________ ms

_________

µ

s

_________

µ

s

_________

_________

µ

s

➀ If a subroutine executes more than once per scan, include each subroutine execution scan time.