Chapter 13
Using Application Specific Instructions

13–14

Operation

The operation of the SQL instruction is shown in the figure below. The
screens shown above the figure are the condensed screens that appear after
instruction entry is complete. Input word I0 is the source. Data in this word
is loaded into integer file #N30 by the sequencer load instruction.

P 0 1 4

S Q L

F I L E

# N 3 0

0

P 0 1 4

S Q L

S R C

I 0

0 0 0 0 H

P 0 1 4

S Q L

R 0 4

L

4

P

2

0000

0101

0000

1010

0

7

8

15

0000

0000

0000

0000

1010

0010

1111

0101

0000

0101

0000

1010

0000

0000

0000

0000

0000

0000

0000

0000

0
1
2
3
4

Step

N30

31
32
33
34

Word

00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15

ON

ON

ON

ON

External Inputs
Associated with I0

Source I0

Sequencer Load File #N30

Current Step

When rung conditions change from false-to-true, the SQL enable bit (EN) is
set. The control element R4 increments to the next position in the sequencer
file and loads the contents of source I0 into the corresponding location in the
file. The SQL instruction continues to load the current data into this location
each scan that the rung remains true. When the rung goes false, the enable
bit (EN) is reset.

The instruction loads data into a new file element at each false-to-true
transition of the rung. When step 4 is completed, the done bit (DN) is set.
Operation cycles to position 1 at the next false-to-true transition of the rung
after position 4.

If the source were a file address such as #N40, files #N40 and #N30 would
both have a length of 5 (0–4) and would track through the steps together per
the position value.