Chapter 19
Common Procedures

19–3

Storing a Program to a Memory Module

You can store the program you currently have loaded in the controller to a
memory module. Follow the steps below.

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Go to the menu and choose the option

MEM MODULE

.

3. Select

STORE PROGRAM

.

S T O R E :

P R O G R A M 1

M E M M O D

F R E E : 0 0 8 K

The name of the program and the amount of memory remaining in the
module is shown.

4. Begin the storing process.

ENT

S T O R E :

P R O G R A M 1

C H E C K I N G . . .

Important: If edits exist in the program, the program is verified for

errors (saved in the controller) before it is stored in the
memory module. Programs with errors cannot be saved
in the controller or stored in the memory module.

Various screens appear to indicate the program is being stored to the
memory module. Once the program is stored, you are returned to the
memory module sub-menu.

Important: If an

OVERWRITE PROG?

confirmation screen or a

MEM

MOD FULL

message appears, see the appropriate section

below.

If an

OVERWRITE PROG?

Confirmation Screen Appears

If a program already exists in the memory module with the same name as the
one you are about to store, a confirmation screen appears asking if you want
to overwrite the existing program. (The memory module acts like a floppy
disk.)

If you want to write over the existing program, press

ENT

. Various screens

appear to indicate the program is being stored to the memory module. Once
the program is stored, you are returned to the memory module sub-menu.