Immediate input with mask (iim) – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 224

Advertising
background image

Chapter 12
Using Program Flow Control Instructions

12–8

This instruction allows you to update data prior to the normal input scan.
Data from a specified input is transferred through a mask to the input data
file, making the data available to instructions following the IIM instruction in
the ladder program.

For the mask, a 1 in an input’s bit position passes data from the source to the
destination. A 0 inhibits data from passing from the source to the
destination.

Entering Parameters

For all micro controllers, specify I0. For 16 I/O controllers, I0/0–9 are valid
and I0/10–15 are considered unused inputs (they do not physically exist).
For 32 I/O controllers, I0/0–15 and I1/0–3 are valid. Specify I1 if you want
to immediately update the last four input bits.

Mask – Specify a Hex constant or register address.

Entering the Instruction

You enter the instruction from within the program monitor functional area.
The following items apply when entering the instruction:

Whenever you see asterisks on the display, the HHP is waiting for data
entry (i.e., a number).

You can return to previously entered operands by pressing this key:

Then if you want to edit that operand, press

DEL

or

FUN-DEL

and enter

new parameters. Press

ENT

to accept the operand and move on to the next

one. Once the entire instruction is entered, if you want to edit the
instruction’s parameters, you must go into the overwrite mode. (See page
17–4.)

P 0 0 7

I I M

A D D R

I 0

0 0 0 0 H

P 0 0 7

I I M

M A S K

O O O B H

IIM

IMMEDIATE INPUT w MASK
Slot

I:O.O

Mask

000B

Execution Times (

µ

sec) when:

True

False

35.72

6.78

Ladder representation:

Immediate Input with Mask
(IIM)

8

3

U

ENT

1

FUN

To enter the function code, press: