After You’ve Entered Your Program

Chapter 18

18–8

Setting the Extended I/O Configuration Bit

When this bit is set to

NO

and unused outputs are written to, the controller

will fault. Therefore, this bit must be set to

YES

if writing to unused outputs.

(For a 16 I/O controller, O/6–O/15 are unused outputs. For a 32 I/O
controller, O/12–O/15 are unused outputs.)

Note: This selection is valid for Series A–C discrete only.

To change the bit setting:

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Access the program configuration menu.

3. Arrow down to the option

EXTEND IO CNFG

and select it.

ENT

6 times

E X T E N D

I O

C N F G

Y E S

N O

4. Select the option

YES

and return to the home screen.

ENT

ESC

ESC

5. You must accept your program edits for this change to take affect. For

information on accepting edits, see page 18–21.