After You’ve Entered Your Program
Chapter 18
18–8
Setting the Extended I/O Configuration Bit
When this bit is set to
NO
and unused outputs are written to, the controller
will fault. Therefore, this bit must be set to
YES
if writing to unused outputs.
(For a 16 I/O controller, O/6–O/15 are unused outputs. For a 32 I/O
controller, O/12–O/15 are unused outputs.)
Note: This selection is valid for Series A–C discrete only.
To change the bit setting:
1. Put the controller in RPRG mode (if it is not already in that mode).
2. Access the program configuration menu.
3. Arrow down to the option
EXTEND IO CNFG
and select it.
ENT
6 times
E X T E N D
I O
C N F G
Y E S
N O
4. Select the option
YES
and return to the home screen.
ENT
ESC
ESC
5. You must accept your program edits for this change to take affect. For
information on accepting edits, see page 18–21.