After You’ve Entered Your Program
Chapter 18
18–16
Configuring the Analog Output
The analog controller’s output channel can be configured to support either
current or voltage operation.
To configure the analog output:
1. Put the controller in RPRG mode (if it is not already in that mode).
2. Access the program configuration menu.
6 times
ENT
3. Arrow up to the option
ANALOG CONFIG
and select it.
2 times
ENT
Note: The function is only available when the Micro Term is attached to an
analog controller.
F I L T E R
S E T T I N G
O U T P U T
C O N F I G
4. Arrow up to the option
OUTPUT CONFIG
and select it.
1 time
ENT
5. Arrow up/down to move between the two settings (0 – 10V or 4 – 20 mA).
6. Enter to store the selected setting and return to the
ANALOG CONFIG
submenu.
ENT
7. Escape to return to the to
ANALOG CONFIG
submenu without storing the
current setting.
ESC