After You’ve Entered Your Program

This chapter shows you the procedures for:

changing the program configuration defaults

accepting your program edits

changing processor modes

monitoring your controller

viewing data table files

using the multi-point function

forcing inputs and outputs

Every default

MICRO

program is configured with the settings shown in the

table below. The table shows the default program configuration settings and
indicates whether you need to save your program for the configuration
changes to take affect.

Program Configuration

Default Setting

Must Save Program

for Change to Take

Affect

See Page

Program Name

MICRO

Yes

18–2

User Password

No password

No

18–2

Master Password

No password

No

18–2

Run Always

No

Yes

18–5

Start-Up Protection

No

Yes

18–6

Fault Override

No

Yes

18–7

Extended I/O Configuration➀

No

Yes

18–8

STI Setpoint

0 (x 10 ms)

No

18–9

STI Enabled

Yes

Yes

18–10

Watchdog Scan

10 (x 10 ms)

No

18–11

Input Filters

8.00 msec for all groups

Yes

18–12

Analog Config

Channel Enable
Filter Setting
Output Config

All Channels Enabled
60 Hz
Voltage Output

Yes

18–14

Lock Program

No

Yes

18–17

Controller Version

Series A and B discrete
controllers

Yes

18–18

Valid for Series A – C discrete only.

Changing the Program
Configuration Defaults