Wiring recommendations, Chapter 2 wiring your controller – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 33
Chapter 2
Wiring Your Controller
2–3
NOT
USED
NOT
USED
I/9
I/10
DC
COM
I/0
I/1
I/2
I/3
I/4
I/5
I/6
I/7
I/8
I/11
I/12
I/13
I/14
I/15
I/16
I/17
I/18
DC
COM
I/19
VDC (+) for Sinking
14–30 VDC
VDC (–) for Sourcing
VDC (+) for Sourcing
14–30 VDC
VDC (–) for Sinking
NOT
USED
NOT
USED
I/9
I/10
DC
COM
I/0
I/1
I/2
I/3
I/4
I/5
I/6
I/7
I/8
I/11
I/12
I/13
I/14
I/15
I/16
I/17
I/18
DC
COM
I/19
VDC (–) for Sourcing
14–30 VDC
14–30 VDC
VDC (+) for Sinking
VDC (–) for Sinking
VDC (+) for Sourcing
Sinking Inputs
Sourcing Inputs
Sinking Inputs
Sourcing Inputs
1761-L32BWB, -L32BBB (Wiring Diagrams also apply to 1761-L20BWB-5A
-L16BWB, -L10BWB, -L16BBB.)
!
ATTENTION: Before you install and wire any device,
disconnect power to the controller system.
The following are general recommendations for wiring your controller
system.
•
Each wire terminal accepts 2 wires of the size listed below:
Wire Type
Wire Size (2 wire maximum per terminal screw)
Solid
#14 to #22 AWG
Stranded
#16 to #22 AWG
Refer to page 2–23 for wiring your high-speed counter.
Important: The diameter of the terminal screw heads is 5.5 mm
(0.220 in.). The input and output terminals of the micro
controller are designed for the following spade lugs:
Wiring Recommendations