Wiring recommendations, Chapter 2 wiring your controller – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 33

Advertising
background image

Chapter 2
Wiring Your Controller

2–3

NOT
USED

NOT
USED

I/9

I/10

DC
COM

I/0

I/1

I/2

I/3

I/4

I/5

I/6

I/7

I/8

I/11

I/12

I/13

I/14

I/15

I/16

I/17

I/18

DC
COM

I/19

VDC (+) for Sinking

14–30 VDC

VDC (–) for Sourcing

VDC (+) for Sourcing

14–30 VDC

VDC (–) for Sinking

NOT
USED

NOT
USED

I/9

I/10

DC
COM

I/0

I/1

I/2

I/3

I/4

I/5

I/6

I/7

I/8

I/11

I/12

I/13

I/14

I/15

I/16

I/17

I/18

DC
COM

I/19

VDC (–) for Sourcing

14–30 VDC

14–30 VDC

VDC (+) for Sinking

VDC (–) for Sinking

VDC (+) for Sourcing

Sinking Inputs

Sourcing Inputs

Sinking Inputs

Sourcing Inputs

1761-L32BWB, -L32BBB (Wiring Diagrams also apply to 1761-L20BWB-5A
-L16BWB, -L10BWB, -L16BBB.)

!

ATTENTION: Before you install and wire any device,
disconnect power to the controller system.

The following are general recommendations for wiring your controller
system.

Each wire terminal accepts 2 wires of the size listed below:

Wire Type

Wire Size (2 wire maximum per terminal screw)

Solid

#14 to #22 AWG

Stranded

#16 to #22 AWG

Refer to page 2–23 for wiring your high-speed counter.

Important: The diameter of the terminal screw heads is 5.5 mm

(0.220 in.). The input and output terminals of the micro
controller are designed for the following spade lugs:

Wiring Recommendations