8 - using basic instructions, Using basic instructions – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 120

Advertising
background image

8

Chapter

8–1

Using Basic Instructions

This chapter contains general information about basic instructions and
explains how they function in your application program. Each of the basic
instructions includes information on:

what the instruction symbol looks like

typical execution time for the instruction

how to use the instruction

how to enter the instruction

In addition, the last section contains an application example for a paper
drilling machine that shows the basic instructions in use.

Bit Instructions

HHP

Display

Mnemonic

Function

Code

Name

Purpose

Page

LD

20

Load

Examines a bit for an On condition. It is the first normally open instruction
in a rung or block.

8–3

LDI

21

Load Inverted

Examines a bit for an Off condition. It is the first normally closed instruction
in a rung or block.

8–4

AND

22

And

Examines a bit for an On condition. It is a normally open instruction placed
in series with any previous input instruction in the current rung or block.
(This differs from the AND output instruction discussed in chapter 10.)

8–3

ANI

23

And Inverted

Examines a bit for an Off condition. It is a normally closed instruction
placed in series with any previous input instruction in the current rung or
block.

8–4

OR

24

Or

Examines a bit for an On condition. It is a normally open instruction placed
in parallel with any previous input instruction in the current rung or block.
(This differs from the OR output instruction discussed in chapter 11.)

8–3

ORI

25

Or Inverted

Examines a bit for an Off condition. It is a normally closed instruction
placed in parallel with any previous input instruction in the current rung or
block.

8–4

LDT

LDT

26

Load True

Represents a short as the first instruction in a rung or block.

8–6

ORT

ORT

27

Or True

Represents a short in parallel with the previous instruction in the current
rung or block.

8–6

OSR

LD OSR

28

One-Shot
Risi

ri ers a

e i e e e

8–7

OSR

AND OSR

29

One-Shot
Rising

Triggers a one-time event.

8–7

( )

OUT

40

Output (Output
Energize)

Represents an output driven by some combination of input logic.
Energized (1) when conditions preceding it permit power continuity in the
rung and de-energized after the rung is false.

8–8

(L)

SET

41

Set (Output
Latch)

Turns a bit on when the rung is executed and this bit retains its state when
the rung is not executed or a power cycle occurs.

8–8

(U

)

RST

42

Reset (Output
Unlatch)

Turns a bit off when the rung is executed and this bit retains its state when
the rung is not executed or when power cycle occurs.

8–8

Continued on following page