Program name

Chapter 20
Troubleshooting Your System

20–16

Fault Code

(Hex)

Recommended Action

Description

Advisory Message

0038

RET IN FILE 2

A RET instruction is in the main
program file (file 2).

Remove the RET instruction
and re-enter RRUN, RCSN, or
RSSN mode.

0040

OUTPUT VERIFY WR

When outputs were written and
read back by the controller, the
read failed. This may have been
caused by noise.

1. Refer to proper grounding

guidelines in chapter 2.

2. Start up your system.
3. Contact your local

Allen-Bradley representative
if the error persists.

0041

EXTRA OUTPUT SET

An extra output bit was set when
the Extend I/O Configuration bit in
the program configuration menu
was reset. For 16-point controllers
this includes bits 6–15. For
32-point controllers this includes
bits 12–15.

1. Set the Extend I/O bit or

change your application to
prevent these bits from
being turned on.

2. Correct the program and

re-enter the RRUN, RCSN,
or RSSN mode.

Valid for Series A – C discrete only.

If the MicroLogix 1000 HHP is disconnected or power failure occurs, the
HHP retains any edits you made to the program before power was removed.
To recover your program with edits, reconnect the HHP to the controller you
were using when power was lost.

Important: If you connect the MicroLogix 1000 HHP to a controller other

than the one you were using while performing program edits,
you will lose your edits.

At the end of the power-up sequence the HHP displays the screen shown
below.

M I C R O

E D I T S

E X I S T

This screen indicates that edits have been made to the program but have not
yet been saved.

Important: If power is removed for more than three days, the retained

program edits may be lost.

If you need to contact Allen-Bradley or your local distributor for assistance,
it is helpful to obtain the following (prior to calling):

controller type, series letter, firmware (FRN) number (see label on side of
controller)

controller LED status

controller error codes (found in S6 of status file)

revision of programming device (on power sequence display of the HHP)

Recovering Your Work

Calling Allen-Bradley for
Assistance