Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 367

Advertising
background image

Chapter 19
Common Procedures

19–8

2. The default setting for the main protocol is DF1.

To accept the default setting (DF1) , press

ENT

.

To change the default setting, arrow right to select DH-485 and then
press

ENT

.

The arrow points to the controller’s current DF1 baud rate.

9 6 0 0

D F 1

2 4 0 0

D F 1

3. Arrow down to the desired DF1 baud rate and select it.

n times

ENT

4. The DF1 node address sub-menu appears next.

D F 1

N O D E

0 – 2 5 4

A D D R : 1

To accept the default setting (1), press

ENT

.

To change the default setting, delete the 1 by pressing

DEL

, type in the

new number, and then press

ENT

.

The arrow points to the controller’s current DH-485 baud rate.

1 9 2 0 0

D H 4 8 5

9 6 0 0

D H 4 8 5

5. Arrow down to the desired DH-485 baud rate and select it.

n times

ENT