This instruction, when its rung is true, stops the controller from scanning the
rest of the program file, updates the I/O, and resumes scanning at rung 0 of
the main program (file 2). If this instruction’s rung is false, the controller
continues the scan until the next TND instruction or the END statement. Use
this instruction to progressively debug a program or conditionally omit the
balance of your current program file or subroutines.

Important: If you use this instruction inside a nested subroutine, execution

of all nested subroutines is terminated.

Do not execute this instruction from the user error fault routine
(file 3), high-speed counter interrupt routine (file 4), or
selectable timed interrupt routine (file 5), or a fault will occur.

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 6

T N D

When this instruction is executed, it causes the controller to enter the
Suspend Idle mode and stores the Suspend ID in word 7 (S7) at the status
file. All outputs are de-energized.

Use this instruction to trap and identify specific conditions for program
debugging and system troubleshooting.

Entering Parameters

Enter a suspend ID number from –32,768 to

+

32,767 when you program the

instruction.

Entering the Instruction

You enter the instruction from within the program monitor functional area.
Asterisks appear on the display to indicate that the HHP is waiting for data
entry (i.e., a number).

P 0 0 4

S U S

I D #

6 0 4

(TND)

Execution Times (

µ

sec) when:

True

False

7.78

3.16

Ladder representation:

Temporary End (TND)

6

3

U

ENT

1

FUN

To enter the function code, press:

SUS

SUSPEND
Suspend ID

604

Execution Times (

µ

sec) when:

True

False

10.85

7.87

Ladder representation:

Suspend (SUS)

7

3

U

ENT

1

FUN

To enter the function code, press: