Chapter 2
Wiring Your Controller

2–22

The following drawings show the analog voltage input range, analog current
input range, analog voltage output range and analog current output range.

Analog Voltage Input Range

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

Operating Range

Overrange

Underrange

–10.5V dc

10.5V dc

–24V dc

24V dc

Analog Current Input Range

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

Operating Range

Overrange

Underrange

–21 mA

21 mA

–50 mA

50 mA

Note: The analog voltage inputs are protected to withstand the application of

24V dc without damage to the controller. The analog current inputs are
protected to withstand the application of

50 mA without damage.

Analog Voltage Output Range

Operating Range

0V dc

10V dc

Analog Current Output Range

Operating Range

20 mA

4 mA

Note: The analog outputs are protected to withstand the short circuiting of
the voltage or current outputs without damage to the controller.

For information on analog signal and data word values using the nominal
transfer function formula, see page 7–4.

Analog Voltage and Current
Input and Output Ranges