Analog voltage and current input and output ranges – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 52
![background image](/manuals/579170/52/background.png)
Chapter 2
Wiring Your Controller
2–22
The following drawings show the analog voltage input range, analog current
input range, analog voltage output range and analog current output range.
Analog Voltage Input Range
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
Operating Range
Overrange
Underrange
–10.5V dc
10.5V dc
–24V dc
24V dc
Analog Current Input Range
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
Operating Range
Overrange
Underrange
–21 mA
21 mA
–50 mA
50 mA
Note: The analog voltage inputs are protected to withstand the application of
24V dc without damage to the controller. The analog current inputs are
protected to withstand the application of
50 mA without damage.
Analog Voltage Output Range
Operating Range
0V dc
10V dc
Analog Current Output Range
Operating Range
20 mA
4 mA
Note: The analog outputs are protected to withstand the short circuiting of
the voltage or current outputs without damage to the controller.
For information on analog signal and data word values using the nominal
transfer function formula, see page 7–4.
Analog Voltage and Current
Input and Output Ranges