Chapter 11
Using Data Handling Instructions

11–20

The value at source A is Exclusive ORed bit by bit with the value at source B
and then stored in the destination.

Truth Table

Dest = A XOR B

A

B

Dest

0

0

0

1

0

1

0

1

1

1

1

0

Source A and B can either be a word address or a constant; however, both
sources cannot be a constant. The destination must be a word address.

Updates to Arithmetic Status Bits

With this Bit:

The Controller:

S0/0

Carry (C)

always resets.

S0/1

Overflow (V)

always resets.

S0/2

Zero (Z)

sets if result is zero; otherwise resets

S0/3

Sign (S)

sets if result is negative (most significant bit is set);
otherwise resets.

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 0

X O R

S R C A

2 5 5

P 0 0 0

X O R

S R C B

N 0

1 0 0

P 0 0 0

X O R

D E S T

N 0

1 0 0

XOR

BITWISE EXCLUS OR
Source A

255

Source B

N7:0

100

Dest

N7:0

100

Execution Times (

µ

sec) when:

True

False

33.64

6.92

Ladder representation:

Exclusive Or (XOR)

ANB

0

ENT

1

FUN

To enter the function code, press:

1

Advertising