Grounding and terminating the dh-485 network, The table below shows connections for belden #9842 – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 58

Chapter 3
Connecting the System
3–5
The table below shows connections for Belden #3106A.
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 – Shield
Blue
Blue
Terminal 3 – (Common)
i e ra e
White with Orange Stripe
Terminal 4 – (Data B)
White/Orange
Orange with White Stripe
Terminal 5 – (Data A)
The table below shows connections for Belden #9842.
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 – Shield
e
i e
White with Blue Stripe
Cut back – no connection
➀
Blue/White
Blue with White Stripe
Terminal 3 – (Common)
i e ra e
White with Orange Stripe
Terminal 4 – (Data B)
White/Orange
Orange with White Stripe
Terminal 5 – (Data A)
➀
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the the insulation jacket is removed. This wire is not used by DH-485.
Grounding and Terminating the DH-485 Network
Only one connector at the end of the link must have Terminals 1 and 2
jumpered together. This provides an earth ground connection for the shield
of the communication cable.
Both ends of the network must have Terminals 5 and 6 jumpered together.
This connects the termination impedance (of 120
Ω
) that is built into each
AIC+ as required by the DH-485 specification.
End-of-Line Termination
Belden #3106A or #9842 Cable
1219 m (4000 ft) Maximum
Jumper
Jumper
Jumper