Configuring the Outer Control Loop

9-7

If

OCL

PROP

TRIM

SELECT

(P.813) is enabled, the signal from the trim range block is

passed through another gain block. The gain of this block is proportional to the
absolute value of the speed reference at the output of the speed loop S-curve block.
The gain of this block ranges from 0 at zero speed to unity gain when the reference is
equal to

TOP

SPEED

(P.011).

You can check the final

OCL

value through

OCL

OUTPUT

(P.848).

OCL

OUTPUT

(P.848)

The output of the
outer control loop in
speed units. This is
the

OCL

trim that is

applied to the
speed/voltage control
loop.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Test Points

OCL

PI

LEAD

FREQ

(P.809)

The lead break
frequency of the
proportional integral
(

PI

) block of the outer

control loop.

Parameter Range:

0.00 to 141.37

RAD

/

S

Default Setting:

1.00

RAD

/

S

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Tuning

If the

OCL

is configured as a type 1 position regulator, set this equal to 0.00

(proportional only).

OCL

PI

NEGATIVE

LIMIT

(P.811)

The negative limit of
the outer control loop

PI

block.

Parameter Range:

0 to 100% of

TOP

SPEED

(P.011)

Default Setting:

100%

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Tuning

OCL

PI

POSITIVE

LIMIT

(P.810)

The positive limit of
the outer control loop

PI

block.

Parameter Range:

0 to 100% of

TOP

SPEED

(P.011)

Default Setting:

100%

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Tuning