8.3.1 Configuring Automatic Field Weakening

The Field Current Regulator kit can provide automatic field weakening. Field
weakening can only be used with speed-regulated drives.

Important: Automatic field weakening cannot be used if

FEEDBACK

SELECT

is set to

ARMATURE

VOLT

.

When

ARMATURE

VOLTAGE

(P.289) exceeds

FLD

WEAKEN

THRESHOLD

(P.518), the field

begins to weaken and the field control loop begins regulating armature voltage. When
field auto weakening is enabled, the drive uses the values of

ARMATURE

VOLTAGE

(P.289) and

FLD

WEAKEN

THRESHOLD

(P.518) to try to maintain a zero input to the first

PI

block. If armature voltage increases, a negative value is input to the

PI

block, which

decreases the high limit to the next

PI

block. This reduces field current, subsequently

lowering the armature voltage, bringing the input to the first

PI

block closer to zero.

If

IR

compensation is used, the threshold where the field control loop begins regulating

armature voltage is

FLD

WEAKEN

THRESHOLD

(P.518) less

IR

COMPENSATION

(P.206) at

rated armature current.

To use automatic field weakening, set

FIELD

AUTO

WEAKEN

(P.517) to

ENABLE

.

To turn off automatic field weakening, set

FIELD

AUTO

WEAKEN

(P.517) to

DISABLE

. If

automatic field weakening is disabled, the field current

PI

block high limit is fixed at 180

degrees.

If needed, you can use

FLD

WEAKEN

LEAD

FREQ

(P.520) and

FLD

WEAKEN

PROP

GAIN

(P.519) to modify the lead frequency and gain of the field auto weaken

PI

block.

MOTOR

HOT

FLD

AMPS

(P.510)

Motor nameplate
value of the rated hot
field amps. This input
is the basis of field
current scaling.

Parameter Range:

0.11 to installed supply rating (4.00, 10.00, or 20.00

amps)

Default Setting:

0.01 amps

Parameter Type:

Configurable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Feedback

Scaling

If the factory defaults are restored, or if a valid value has not yet been entered for
this parameter, the DC field voltage is fixed at 150 V on a 230VAC line, or at 300V
on a 460VAC line.

!

ATTENTION: The incorrect configuration of this parameter can cause a
motor overvoltage condition. Configure

MOTOR

HOT

FLD

AMPS

(P.510) to

the motor nameplate value. Failure to observe this precaution can result
in bodily injury and damage to the equipment.

!

ATTENTION: The incorrect configuration of the parameters for this loop
can cause a motor overvoltage condition. Configure

MOTOR

HOT

FLD

AMPS

(P.510) to the motor’s nameplate value. Failure to observe this precaution
can result in bodily injury and damage to the equipment.