P.517), P.587), P.512) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 93

Advertising
background image

Configuring the Field Supply

8-9

FIELD

AUTO

WEAKEN

(P.517)

Enables or disables
automatic field
weakening by the
field control loop.
When it is disabled,
the field current

PI

block high limit is
fixed at 180 degrees.

Parameter Range:

DISABLED

ENABLED

Default Setting:

DISABLED

Parameter Type:

Configurable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Configure

If

FEEDBACK

SELECT

is set to

ARMATURE

VOLT

, this is automatically set to

DISABLED

and cannot be changed.

FIELD

DELTA

HIGH

LIM

(P.587)

High limit of the field
current

PI

block.

Parameter Range:

0 to 180

DEGREE

Default Setting:

130

DEGREE

Parameter Type:

Configurable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Configure

FIELD

LOSS

THRESHOLD

(P.512)

The value that is
compared to

FIELD

FEEDBACK

(P.589) to

check for field loss.

Parameter Range:

50 to 100% of

MOTOR

HOT

FLD

AMPS

(P.510) when

FEEDBACK

SELECT

(P.200) is set to

ARMATURE

VOLT

0 to 100% of

MOTOR

HOT

FLD

AMPS

(P.510) when

FEEDBACK

SELECT

(P.200) is set to

DC

TACH

,

PULSE

TACH

, or

AC

TACH

Default Setting:

60% of

MOTOR

HOT

FLD

AMPS

(P.510)

Parameter Type:

Configurable

OIM Menu Path(s):

Field – Field Current Regulator – Field Loop

Configure

FIELD

LOSS

THRESHOLD

is set as a percentage of

MOTOR

HOT

FLD

AMPS

. It is usually

set to 85% of the motor nameplate field weaken current.