Troubleshooting the FlexPak 3000 Drive

13-1

C

HAPTER

13

Troubleshooting the FlexPak 3000 Drive

This section provides lists of faults and alarms that can occur and the possible causes.
It also lists parameters that can be helpful when troubleshooting.

For instruction on how to clear faults and alarms, see the FlexPak 3000 Drive
Operator Interface Module (

OIM

) User Guide (D2-3344).

13.1 Fault and Alarm Messages, Descriptions,

and Code Numbers

Table 13.1 lists fault codes and table 13.2 lists alarm codes. The codes are in numeric
order by the number you see on the

OIM

display when an alarm or fault occurs.

!

ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, operate, or service this equipment. Read and understand
this section in its entirety before proceeding. Failure to observe this
precaution could result in severe bodily injury or loss of life.

Table 13.1 – Fault Codes

Code

OIM Display

Description

F00001

IET

(

OVERCURRENT

)

Armature current instantaneously exceeded 180% of

MAXIMUM

CURRENT

.

Possible causes:

Incorrect armature current feedback scaling (

MOTOR

RATED

ARM

AMPS

,

MAXIMUM

CURRENT

,

CT

TURNS

RATIO

, or J18 not set properly).

One or more thyristors not operating.

Improper current minor loop tuning.

Motor armature winding damaged.