FlexPak 3000 DC Drive Software Reference

4.

A zero reference is input to the current minor loop reference path.

5.

The drive waits until armature current reaches discontinuous conduction.

6.

The main contactor is opened and the DB contactor is closed.

Current Limit Stop Sequencing

Current limit stop sequencing is used when one of these conditions occurs:

an active stop input is asserted,

STOP

MODE

SELECT

(P.114) is set to

CURRENT

LIMIT

,

and the drive is in run mode

the jog input is deasserted when the drive is in jog mode and

STOP

MODE

SELECT

(P.114) is set to

CURRENT

LIMIT

. Deasserting the jog input will not initiate the stop

sequence until the speed feedback is less than or equal to

STOP

SPEED

THRESHOLD

(P.113) or until the

JOG

OFF

DELAY

TIME

(P.121) is exceeded, whichever occurs last.

In a current limit stop sequence:

1.

From run mode: A zero reference is input to the speed loop reference path at the
speed loop summing junction.

From jog mode: A zero reference is input to the jog reference ramp block.

2.

Jog mode only: The jog reference ramps toward zero at the rate set by

JOG

ACCEL

/

DECEL

TIME

(P.013).

3.

The drive waits until speed feedback falls below

STOP

SPEED

THRESHOLD

(P.113).

If the drive is regenerative (S6R), this phase of the current limit stop sequence
takes little time. If the drive is non-regenerative (S6), the motor coasts during this
phase of the current limit stop sequence.

4.

A zero reference is input to the current minor loop reference path.

5.

The drive waits until armature current reaches discontinuous conduction.

6.

The main contactor is opened and the DB contactor is closed.