Configuring the Speed/Voltage Loop

5-15

NEG

CURRENT

LIM

SEL

(P.224)

Selects the source for
the negative current
limit.

If

REGISTER

is

selected,

NEGATIVE

CURRENT

LIM

(P.006)

is used as the limit.

Parameter Range:

REGISTER

ANALOG

IN

1

ANALOG

IN

2

NETW

IN

REG

1

NETW

IN

REG

2

NETW

IN

REG

3

Default Setting:

REGISTER

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) - Speed/Voltage Loop

(

SPD

) Tuning

Current Minor Loop (

CML

) -

CML

Tuning

The I/O Expansion kit must be installed to use

ANALOG

IN

1 (terminals 50 and 51 on

the I/O Expansion board) or

ANALOG

IN

2 (terminals 52 and 53).

A network kit must be installed to select the network input registers (

NETW

IN

REG

1,

2, or 3). Note that the network input registers are updated only when Control
Source (P.000) is set to

NETWORK

and the network is active.

This parameter is affected by

NEG

CUR

LIM

INV

EN

(P.226).

NEG

CUR

LIM

INV

EN

(P.226)

Enables or disables
the negative current
limit inverter to the
speed loop PI block
low limit input.

Parameter Range:

DISABLED

ENABLED

Default Setting:

ENABLED

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

When this parameter is set to

ENABLED

,

POSITIVE

CURRENT

LIM

(P.005) and

NEGATIVE

CURRENT

LIM

(P.006) are restricted to positive values.

When this parameter is set to

DISABLED

, the range of

NEGATIVE

CURRENT

LIM

(P.006)

is restricted to negative values.

When you change this parameter value:

Alarm A00052 occurs.

The parameters

NEG

CURRENT

LIM

SEL

(P.224) and

POS

CURRENT

LIM

SEL

(P.223)

are automatically set to

REGISTER

.

NEGATIVE

CURRENT

LIM

(P.006) is inverted. For example, if

NEG

CUR

LIM

INV

EN

is

set to

ENABLE

and

NEGATIVE

CURRENT

LIM

is set to 150%

FLA

, changing

NEG

CUR

LIM

INV

EN

to

DISABLED

changes the value of

NEGATIVE

CURRENT

LIM

to –150%

FLA

.

Carefully check your current limit scheme and the values of

POSITIVE

CURRENT

LIM

(P.005) and

NEGATIVE

CURRENT

LIM

(P.006) to avoid unintended drive operation.