13-14

FlexPak 3000 DC Drive Software Reference

13.4 SCR Diagnostics and Adjusting Open

SCR Sensitivity

Under normal drive operation, the load carried by each

SCR

is relatively equal, as

shown in figure 13.1.

If one or more

SCR

s fail to turn to on, a unique pattern of insufficient or missing current

pulses results, as shown in figure 13.2.

Open

SCR

diagnostics detects

SCR

s that are not conducting by analyzing the level of

current produced by each

SCR

pair firing. If one or more

SCR

consistently fails to

produce current at a level approximately equal to other

SCR

s that fired, the drive

concludes that an open

SCR

has occurred.

The open

SCR

diagnostic calculates the percentage deviation of current feedback for

each pair of

SCR

s from the average current feedback. The percent deviation must

exceed the value set for

OPEN

SCR

SENSITIVITY

(P.600) before the diagnostic proceeds

to the next part of the diagnostic.

In the next part of the diagnostic, deviations from the average current are integrated
over time to eliminate transient effects from the calculation. When the integration
reaches the value of

OPEN

SCR

TRIP

THRESH

(P.601), an open

SCR

fault is generated.

If you are experiencing nuisance

SCR

faults, you can use these parameters to increase

the tolerance to conditions that could trigger an open

SCR

fault.