Configuring a Network

10-5

NETW

OUT

REG

3

SELECT

(P.904)

Selects the
parameter to be
monitored.

Parameter Range:

–32768 to 32767

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Network Communications

Select the parameter to monitor by configuring the parameter number. For example,
setting this parameter equal to 588 will write the value of parameter

FIELD

DELTA

(P.588) to the installed network register.

NETW

IN

REG

1 (P.905)

Indicates the value
being written by the
network master.

Parameter Range:

–32768 to 32767

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Network Communications

For the AutoMax network, this parameter writes to Drop_1, register 34. For the
ControlNet network, this parameter writes to file address N11:10.

NETW

IN

REG

2 (P.906)

Indicates the value
being written by the
network master.

Parameter Range:

–32768 to 32767

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Network Communications

For the AutoMax network, this parameter writes to Drop_1, register 35. For the
ControlNet network, this parameter writes to files address N11:11.

NETW

IN

REG

3 (P.907)

Indicates the value
being written by the
network master.

Parameter Range:

–32768 to 32767

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Network Communications

For the AutoMax network, this parameter writes to Drop_1, register 36. For the
ControlNet network, this parameter writes to file address N11:12.