Configuring Parameters for Winding Applications

These options are only available when using the AutoMax Network Communication
board (

CONTROL

SOURCE

SELECT

is set to

NETWORK

and

NETW

REGISTER

MAP

SEL

(P.914) is set to 2 (

ALTERNATE

)) or when using the ControlNet Network Communication

board.

For diameter-dependent loads, you can scale the feedback to the speed loop. The
feedback is scaled through a multiplier block. The operation of the multiplier block is:

Where:

A is a speed feedback multiplier (gain)

B is the speed feedback from the lead/lag block output

When

NETW

REGISTER

MAP

SEL

(P.914) is set to

ALTERNATE

, the source for A is the

network register

SPEED

FEEDBACK

GAIN

(alternate map, Drop_1, register 38). Even if

the multiplier block is not being used, you must write a value of 1000 to the

SPEED

FEEDBACK

GAIN

register whenever writing to Drop_1. This sets the multiplier block to

unity gain.

If the web is underwound, set

UNDERWIND

ENABLE

(alternate map, Drop_1, register 32,

bit 5) to

ENABLE

. This enables two inverters, one in the speed loop feedback path

immediately before the feedback summing junction, and one at the input to the

CML

limit block.

Refer to the appropriate network communication manual for register map
assignments.

A

B

1000

-------------