FlexPak 3000 DC Drive Software Reference

6.1

Configuring Inertia Compensation

INERTIA

COMP

SELECT

(P.221)

Selects the source of
the inertia
compensation signal.

The analog input
choices are only
available if the I/O
Expansion kit is
installed.

Parameter Range:

NONE

INTERNAL

ANALOG

IN

1

ANALOG

IN

2

NETW

IN

REG

1

NETW

IN

REG

2

NETW

IN

REG

3

Default Setting:

NONE

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) - Speed/Voltage Loop

(

SPD

) Tuning

When

INTERNAL

is selected, the inertia compensation signal is generated by scaling

the rate output from the speed/voltage loop S-curve block based on the combined
inertia of the motor and its connected load.

Inertia compensation circuit supports constant diameter, constant field current
applications. The compensation signal is summed with the speed/voltage loop

PI

block output to form the reference to the

CML

.

When

INTERNAL

is selected, rate output from the speed/voltage loop S-curve block

is scaled based on the combined inertia of the motor and its connected load, as set
through the

NORMALIZED

INERTIA

(P.222).

A network kit must be installed to select the network input registers (

NETW

IN

REG

1,

2, or 3). Note that the network input registers are updated only when Control
Source (P.000) is set to

NETWORK

and the network is active.

MAXIMUM

CURRENT

(P.007)

The highest amount
of current (positive or
negative) for a given
application.

This input is the basis
of armature current
scaling.

Parameter Range:

25 to 200 %

FLA

Default Setting:

150 %

FLA

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (

CML

) -

CML

Feedback Scaling

MAXIMUM

CURRENT

is limited to 200% of

MOTOR

RATED

ARM

AMPS

.

The setting of

MAXIMUM

CURRENT

can affect the value of

J

18

ARM

I

FB

RESISTOR

(P.395). Check

J

18

ARM

I

FB

RESISTOR

(P.395) and the setting of the J18 jumper if

you change

MAXIMUM

CURRENT

.