P.606) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 132

Advertising
background image

12-4

FlexPak 3000 DC Drive Software Reference

LEVEL

DETECT

2

THRESH

(P.606)

The threshold for
level detector 2.

Parameter Range:*

0.1 to 100.0% or

MAXIMUM

CURRENT

Default Setting:

10.0%

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Level Detectors

When the absolute value of the signal driving level detector 2 is greater than or
equal to this threshold, the associated timer starts. If the input signal is less than
this threshold, the timer is immediately reset and the level detector output is set to

OFF

.

*The parameter range for the level detector is automatically rescaled for speed or
current based on the input selected by

LEVEL

DETECT

2

SELECT

(P.605). If

CML

FEEDBACK

is selected for

LEVEL

DETECT

2

SELECT

, the parameter range is 0.1 to

MAXIMUM

CURRENT

. For any other

LEVEL

DETECT

2

SELECT

settings, the parameter

range is 0.1 to 100.0%.