P.418), P.419), P.422) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 125

Advertising
background image

Configuring Parameters for the I/O Expansion Kit

11-9

ANLG

OUT

1

SELECT

(P.418)

Selects the signal
used to drive analog
output 1 (terminals
54 and 55 on the I/O
Expansion kit).

Parameter Range:

See table 11.1 for options

Default Setting:

ZERO

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Analog I/O

When the analog output is at its maximum value, the selected signal is at its full
scale value.

ANLG

OUT

1

SIG

TYPE

(P.419)

Selects the type of
signal to be
generated by analog
output 1 (terminals
54 and 55 on the I/O
Expansion kit).

Parameter Range:

0– 10 V
+/–10 V
4-20 mA

Default Setting:

+/–10 V

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Analog I/O

This setting must match the I/O Expansion kit J14 and J15 settings.

ANLG

OUT

2

GAIN

ADJ

(P.422)

Adjusts the gain of
analog output 2
(terminals 56 and 57
on the I/O Expansion
kit) to allow it to
produce a signal from
5.0 to the full scale
value of
approximately
13.0 VDC.

Parameter Range:

0.500 to 1.300

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Analog I/O

The full scale value is determined by

ANLG

OUT

2

SELECT

. See table 11.1.

This is typically used to adjust the 10 V full scale output to match the input voltage
requirements of attached equipment. For example, set this parameter to 0.800 for
equipment that accepts a ±8 VDC signal.

The outputs are rated to 10 VDC, so gain adjust values greater than 1.000 might
cause the analog output circuit to saturate.

Analog output 2 only generates a ±10 VDC input signal and cannot be changed.

Analog output 1 and 2 are only rated to 10 VDC, so gain adjustment values greater
than 1.000 might cause the analog output circuit to saturate.