Configuring the Metering Outputs

7-3

METER

OUT

2

GAIN

ADJ

(P.401)

Scales the meter
output 2 signal at the
Regulator board
terminal strip.

Parameter Range:

0.100 to 1.900

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Meter Outputs

METER

OUT

2

SELECT

(P.405) can be set to

FULL

SCALE

for an accurate gain

adjustment. See figure 7.1.

Adjust the zero point (

METER

OUT

2

ZERO

ADJ

(P.403)) before adjusting gain.

METER

OUT

2

SELECT

(P.405)

Selects the drive
output that will source
meter output 2
(terminals 25 and 26
on the Regulator
board).

Parameter Range:

See table 7.1 for options

Default Setting:

SPD

LOOP

FEEDBACK

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Meter Outputs

METER

OUT

2

ZERO

ADJ

(P.403)

Removes any offset
from the meter
output 2 signal at the
Regulator board
terminal strip.

Parameter Range:

–200 to 200

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Meter Outputs

METER

OUT

2

SELECT

(P.405) can be set to

ZERO

for an accurate zero adjustment.

See figure 7.1.