Configuring the Metering Outputs
7-3
METER
OUT
2
GAIN
ADJ
(P.401)
Scales the meter
output 2 signal at the
Regulator board
terminal strip.
Parameter Range:
0.100 to 1.900
Default Setting:
1.000
Parameter Type:
Tunable
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
2
SELECT
(P.405) can be set to
FULL
SCALE
for an accurate gain
adjustment. See figure 7.1.
Adjust the zero point (
METER
OUT
2
ZERO
ADJ
(P.403)) before adjusting gain.
METER
OUT
2
SELECT
(P.405)
Selects the drive
output that will source
meter output 2
(terminals 25 and 26
on the Regulator
board).
Parameter Range:
See table 7.1 for options
Default Setting:
SPD
LOOP
FEEDBACK
Parameter Type:
Tunable
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
2
ZERO
ADJ
(P.403)
Removes any offset
from the meter
output 2 signal at the
Regulator board
terminal strip.
Parameter Range:
–200 to 200
Default Setting:
0
Parameter Type:
Tunable
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
2
SELECT
(P.405) can be set to
ZERO
for an accurate zero adjustment.
See figure 7.1.