Configuring the Field Supply

8-3

FIELD

ECONOMY

DELAY

(P.501)

After the motor stops,
the drive maintains
full field for

FIELD

ECONOMY

DELAY

minutes before
entering field
economy.

Parameter Range:

0 to 27 minutes

Default Setting:

5 minutes

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Standard/enhanced Field Supply
Field - Field Current Regulator - Field Loop Configure

When the motor starts again, the drive immediately returns to full field.

FIELD

ECONOMY

DELAY

does not affect operation of the standard field supply. Field

economy cannot be disabled.

This parameter has no effect when the Enhanced Field Supply kit or standard field
supply is installed.

FIELD

ECONOMY

REF

(P.511)

Only available if the
Field Current
Regulator kit is
installed.

Parameter Range:

0 to 100%

Default Setting:

0%

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Configure

The percentage of

MOTOR

HOT

FLD

AMPS

(P.510) set as a reference for field

economy mode. This parameter must be set above the

FIELD

LOSS

THRESHOLD

(P.512) value to avoid field loss faults.

This parameter has no effect when the Enhanced Field Supply kit or standard field
supply is installed.

FIELD

REF

REGISTER

(P.513)

Current reference for
the field control loop.
This is the field
current reference
when the drive is not
in field economy.

Parameter Range:

0 to

MOTOR

HOT

FLD

AMPS

Default Setting:

MOTOR

HOT

FLD

AMPS

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning

FIELD

REF

REGISTER

should be set greater than

FIELD

LOSS

THRESHOLD

(P.512) to

avoid

FIELD

LOSS

faults.

Only available if the Field Current Regulator kit is installed.