Configuring the Speed Reference

4-23

4.4

Final Speed Reference Logic

In the last part of the speed reference, the signals from the speed reference ramp and
current minor loop are summed and limited by

TOP

SPEED

to determine the speed

reference sent to the speed loop. The final value that is sent to the speed loop is the

SPD

LOOP

REFERENCE

(P.295). The block diagram is shown in figure 4.7.

STOP

MODE

SELECT

(P.114)

Selects how the drive
responds to a normal
stop command.
Opening a
permissive input will
always cause a coast
stop.

Parameter Range:

RAMP

COAST

/

DB

CURRENT

LIMIT

Default Setting:

COAST

/

DB

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

If the drive is configured as a current regulator, only

COAST

/

DB

can be selected.

STOP

SPEED

THRESHOLD

(P.113)

Configures the
threshold speed
below which the main
contactor will
automatically open
after a ramp stop or
current limit stop is
asserted.

Parameter Range:

0 to

MAXIMUM

SPEED

(

RPM

or user-defined units

Default Setting:

50

RPM

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Figure 4.7 – Speed Reference Mode Select Block Diagram

From Figure 4.5, Speed Reference

Ramp Block Diagram

From Figure 9.1,

Outer Control

Loop Block Diagram

To Figure 5.1,

Speed

Loop Block Diagram