P.900), P.902), P.903) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 110

Advertising
background image

10-4

FlexPak 3000 DC Drive Software Reference

NETW

DROP

NUMBER

(P.900)

Network Drop
Number. Selects the
base drop number
the network option
board will respond to
on the network.

NETW

DROP

NUMBER

cannot be changed
through the network.

Parameter Range:

For AutoMax Network Communication kit:

1 to 55 if

NETW

CONNECT

TYPE

=

BASIC

;

1 to 52 if

NETW

CONNECT

TYPE

=

FULL

For DeviceNet Interface kit: 0 to 63 (

NETW

CONNECT

TYPE

value does not affect)

For ControlNet Network Communication kit: 1 to 99

(

NETW

CONNECT

TYPE

value does not affect)

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Network Communications

When

NETW

CONNECT

TYPE

(P.910) is set to

FULL

, the AutoMax Network

Communication kit occupies multiple network drops beginning at

NETW

DROP

NUMBER

. The number of drops occupied (drop depth) affects the upper limit of

NETW

DROP

NUMBER

. See

NETW

CONNECT

TYPE

(P.910), to determine drop depth.

NETW

OUT

REG

1

SELECT

(P.902)

Selects the
parameter to be
monitored.

Parameter Range:

–32768 to 32767

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Network Communications

Select the parameter to monitor by configuring the parameter number. For example,
setting this parameter equal to 588 will write the value of parameter

FIELD

DELTA

(P.588) to the installed network register.

NETW

OUT

REG

2

SELECT

(P.903)

Selects the
parameter to be
monitored.

Parameter Range:

–32768 to 32767

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Network Communications

Select the parameter to monitor by configuring the parameter number. For example,
setting this parameter equal to 588 will write the value of parameter

FIELD

DELTA

(P.588) to the installed network register.