Troubleshooting the FlexPak 3000 Drive

13-17

Step 10. Set

PHASE

FIRE

TEST

DELTA

(P.309) to 55 degrees. Slowly increase

PHASE

FIRE

TEST

DELTA

until a steady pattern of “bumps” appears on the

oscilloscope. If all thyristors in the selected bridge are operating, there will
be six bumps per AC line cycle, similar to the example in figure 13.1. If any
bumps are missing, one or more thyristors are not conducting, similar to the
example in figure 13.3.

Note that conduction will not begin until the firing angle is sufficiently
advanced (

PHASE

FIRE

TEST

DELTA

(P.309) more than 60 degrees). A rate

limit block limits the rate of change of firing angle advances to prevent
sudden increases in current. To prevent the drive from entering continuous
conduction during this test,

PHASE

FIRE

TEST

DELTA

(P.309) should not

exceed 89 degrees.

Step 11. Press

to stop the armature phase fire test.

Step 12. Turn off power to the drive (lockout and tag as necessary).

Step 13. Either unlock the motor armature or remove the dummy load and reconnect

the motor armature leads.

If the motor field winding was disconnected, reconnect it and return jumper
J20 to its original position (typically

ENABLE

).

Figure 13.3 – Thyristors Fail to Conduct